Cold snaps place additional demands on heating systems and can expose existing problems such as blocked filters, dirty coils, worn belts and faulty sensors. These issues can lead to callouts, uneven temperatures and unnecessary energy use.
A planned winter-readiness programme helps reduce the risk of breakdowns and unnecessary energy use. Use the checklist alongside manufacturers’ maintenance instructions and your site-specific planned preventive maintenance (PPM) schedule, with separate provision for applicable F-Gas obligations.
If you manage multi-site estates or a critical environment, use this as a template you can drop straight into your PPM planner.
Winter preparation focuses on airflow, heat transfer, moving parts, drainage, sensors, safety devices and the Building Management System(BMS). The checklist below should be tailored to the equipment installed and completed by a competent engineer.
Following the visit, customers should receive a clear service report with test results, priority defects and recommended remedial actions. Identify any additional repairs or specialist deep cleaning, with costs for approval where these fall outside the agreed maintenance scope.
1. Filters and airflow:
- Clean reusable filters in accordance with manufacturers’ instructions and replace disposable filters as required.
- Check filter frames, clips, and door seals to eliminate bypass.
- Record differential pressure before and after to validate improvement.
2. Coils and heat transfer:
- Clean heating coils and any upstream strainers.
- Verify valve operation and actuator travel.
- Record entering- and leaving-air temperatures and verify airflow to assess heating performance.
3. Fans, belts, and bearings:
- Measure motor amps against nameplate.
- Inspect bearings for heat or noise; lubricate where applicable.
- Replace stretched or glazed belts and set correct tension and alignment.
4. Drains and condensate management:
- Remove biofilm from pans.
- Flush lines and confirm free discharge.
- Prime U-traps and test pump operation where fitted.
5. Dampers and weather louvres:
- Clear leaves and debris from louvres.
- Prove actuator stroke, close-off, and seal integrity.
- Verify fresh-air delivery against the building’s ventilation requirements and occupancy while avoiding unnecessary energy use.
6. Sensors, frost, and safeties:
- Function-test frost stats and verify trip setpoints.
- Check supply, return and outside-air sensor accuracy against a suitable reference and recalibrate or replace where necessary.
- Confirm differential pressure switches and high limits operate and alarm.
7. BMS setpoints and strategies:
- Review time schedules for winter occupancy.
- Confirm night set-back and optimum-start.
- Validate frost protection logic and alarms route to the right responders.
- Check exposed water pipework insulation, trace heating where fitted, and glycol concentration where specified.
8. Documentation and compliance evidence:
- Log all findings, parts replaced and actions outstanding.
- For systems containing F-Gas refrigerants, keep required records current and complete statutory leak checks where applicable, at intervals appropriate to the equipment, refrigerant charge and applicable regulations. Record engineer certification details.
- Store photos and test readings in your central maintenance system for audits.
Air conditioning used for heating:
- For split and variable refrigerant flow (VRF) systems, check heating operation, room temperatures, controller settings and schedules against manufacturers’ guidance.
- Inspect indoor filters, heat exchangers and fan assemblies. Cleaning filters alone may not restore performance if internal components remain dirty. Restricted airflow and dirty heat exchangers can reduce useful heat output and increase running time and energy use. Recommend specialist deep cleaning where condition requires it.
- Inspect outdoor heat exchangers, airflow clearances and drainage, and check defrost operation and winter requirements in accordance with manufacturers’ instructions.

Service frequency should reflect manufacturers’recommendations, operating hours, site conditions, asset condition and theconsequences of failure. Twice-yearly visits may be a suitable starting pointfor some offices and retail sites, but should not be treated as a universalstandard. More frequent visits or interim checks may be needed for:
- Heavy dust or pollution near intakes
- 24/7 operation or critical temperature control
- Healthcare, education, and high-occupancyenvironments
Schedule deeper services ahead of seasonal peaks. Reviewfrequencies against filter condition, operating readings and fault history, andincrease checks where needed. Routine servicing and statutory F-Gas leak checksare separate requirements; confirm the applicable leak-check intervals for eachrefrigerant system.
- Map assets to a winter maintenance window. Prioritise air handling units (AHUs) serving critical spaces, year-round server-room cooling and plant with previous frost trips.
- Bundle tasks with other compliance items to reduce disruption. If you manage multi-site portfolios, coordinate dates, access, and reporting so findings roll into one dashboard.
- Use last winter’s alarms and trend data to focus checks on problem units.
If you are building or refreshing your PPM approach, see our guide to planned preventive maintenance for facilities teams.
Recognising symptoms early allows faults to be investigated before they develop into a breakdown. Watch for:
- Rising filter pressure or sudden airflow drops.
- Uneven temperatures, cold spots, or frequent frost trips
- Condensate leaks, musty odours, or persistent or excessive icing that does not clear through normal defrost operation. Temporary frost on outdoor heat-pump coils is normal during heating.
- Unusual fan noise, vibration, or hot bearings
- BMS trends drifting from setpoints or frequent short cycling.
Act promptly when these appear to avoid downtime and higher repair costs.
- Reactive maintenance: fix on failure. Suitable only for non-critical, low-cost items.
- Preventive maintenance: time or run hour-based tasks. The backbone of winter readiness.
- Predictive or condition-based: decisions led by readings and trends such as vibration, differential pressure, temperature deltas. Ideal for belts, bearings, and coils.
- Reliability-centred: strategy based on consequence and probability of failure. Useful for critical estates and where you need evidence for budget decisions.
Most estates blend preventive and condition-based tasks, with reactive reserved for unavoidable failures.
Keep records tight. Service sheets, calibration results, photos, and remedial notes form your audit trail. For plant containing F-Gas refrigerants, maintain required records and statutory leak checks where applicable, and ensure refrigerant work is carried out by appropriately qualified and certified personnel. Keep AHU maintenance records alongside applicable ventilation-cleaning, fire-damper inspection and water-hygiene records.
Even with strong PPM, keep a clear escalation path for freezing conditions. Confirm who receives BMS frost alarms, how engineers can access the site out of hours, and where spares such as belts and filters are held. Rapid communication helps reduce downtime when weather turns.
- What does HVAC maintenance involve? Inspection, cleaning and testing of filters, coils, fans, belts, drains, sensors, safeties, and controls, plus BMS verification, documentation, and where applicable F-Gas checks.
- How often should you service commercial HVAC? Follow manufacturers’ recommendations and a site-specific maintenance plan based on use, environment, condition and risk. Confirm statutory F-Gas leak-check intervals separately.
- What are signs of HVAC problems? Airflow loss, temperature drift, frost trips, leaks, unusual noise or vibration, and off-trend BMS data.
- What are the four maintenance types in HVAC? Reactive, preventive, predictive or condition-based, and reliability-centred.